AEPE
Product Categories
Switchgears
Load Break Switches
Circuit Breakers
Branch Cabinets
Accessories
Product Search
 
AGN-12/24 SF6 Ring main unit---AEPE
AGN-12/24 SF6 Ring main unit
Product Brochure User's Manual
Service conditions Classic combination

 
VS1

VDM6

BP1

AFL-12/24

 Core switch elements in AGN



??????

 

AGN-12/24 Ring main unit

 

       

Specification
   

No.

Item  AGN-12

Unit

Parameters

1

Rated voltage

kV

12

24

2

Rated current

A

630 / 1250 *

3

Rated frequency

Hz

50 / 60

4

1min Power frequency withstand voltage

Common value

kV

42

50

Across insulate distance

kV

48

60

5

Lightning impulse withstand  voltage

Common value

kV

75

125

Across insulate distance

kV

85

145

6

Rated short time withstand current

Main loop

kA

25 / 2s

20/2s

Earth loop

kA

20 / 2s

16/2s

7

Rated withstand current ( peak)

kA

63

50

8

Rated transfer current

A

1700

1000

9

Rated active load and close circuit breaking current

A

630

10

Rated cable charge breaking current

A

50 and 10

11

Unloaded transformer breaking current

A

20

20

12

Cable charge breaking current in earthing malfunction

A

100

80

13

Rated short circuit breaking current

kA

20**

 

14

Rated short circuit making current

kA

63

50

15

Protection degree

 

IP3X

16

Load break switch life

Times

5000

17

Earth switch life

Times

2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

        **  with fuse combination  * rated current of fuse combination decided by the fuse current       

General Description

AGN-12/24 SF6 ring main unit with SF6 load switch as the main switch and air insulation for whole cabinet is electric distribution automatization and compact also expandable metal clad switchgear, it character in it's simple strucuture, flexible operation, reliable interlocking and convenient installation etc., which can provide the satisfactory technical projects both for different application occasions and users.

With the adoption of sensor technology and the protection relay up to date, plus the advanced technology and flexible assembly project, AGN-12 unit type SF6 ring main unit can completely meet the requirement of continuously variable market. It can take self-produced AFL-12/24D load break switch or ABB SFG type SF6 load break switch; also according to user's demand can be assembled with the Ukraine BP series vaccum circuit breaker with permanent magnetic mechanism. Operational methods for the main switch inside ring main unit can be either manual or electric power driven. And it can meet the requirement of "Four Controls" when matched with FTU,RTU.

This product conforms to the standards of IEC62271-100 and GB3804,3906.11022, IEC298,265,129,694,420,56,529,932

cn
© 2007 Aepe.biz [Sie Manage Powered by Seasky Networks.]