SRM16-12/24 SF6 GIS RMU---AEPE
| SRM16-12/24 SF6 GIS RMU |
|
Core circuit breakers in SRM16 |
SRM16-12/24 SF6 Gas Insulate Switchgear
|
|
Specification
|
No |
Item SRM16 |
Unit |
C Module |
V Module |
|
Load Break Switch |
Circuit Breaker |
|
1 |
Rated voltage |
kV |
12 |
24 |
12 |
24 |
|
2 |
Rated current |
A |
630* |
|
3 |
Rated frequency |
Hz |
50/60 |
|
4 |
1min Power frequency withstand voltage |
Common value |
kV |
42 |
50 |
42 |
50 |
|
Across insulate distance |
kV |
48 |
60 |
48 |
60 |
|
5 |
Lightning impulse withstand voltage |
Common value |
kV |
75 |
125 |
75 |
125 |
|
Across insulate distance |
kV |
85 |
145 |
85 |
145 |
|
6 |
Rated transfer current |
A |
1700 |
1000 |
|
|
|
7 |
Rated active load and close circuit breaking current |
A |
630 |
|
8 |
Rated cable charge breaking current |
A |
50 and 10 |
|
9 |
Rated short circuit breaking current |
kA |
|
|
20 |
16 |
|
10 |
Rated short circuit making current (peak) |
kA |
63 |
50 |
63 |
50 |
|
11 |
Short time (2s) withstand current, load switch/earth |
kA |
25/20 |
20/20 |
25/20 |
20/20 |
|
12 |
Rated withstand current (peak) |
kA |
63 |
50 |
63 |
50 |
|
13 |
Mechanism life |
Times |
3000 |
10000 |
3000 |
|
14 |
Dimension ( per unit) |
mm |
371x751x1336 |
|
|
Remarks * Rated current of combination of switch and fuse decided by the fuse current.
|
By the perfect integration of stationary type and flexible expansion, SRM16-12 type SF6 gas-insulating compact close metal switchgear with the adoption of the modular design, is suitable for end-user or network node, meanwhile meets the requirement of all kinds of switching substations?cabinet-type transformer substations and cable branch cabinets. It characters on its compact structure, safety and reliability,longevity and maintenance free.
This product is in conformity with the standards of IEC60420,GB/T11022,GB3804,GB3906 | |
|
|
|