ADF-630 Outdoor cable cabinet---AEPE
| ADF-630 Outdoor cable cabinet |
|
|
other switches
|
ADF-630 outdoor cable branch cabinet
|
|
Specification
|
No |
Item |
Unit |
Parameters |
|
ADF-630 type |
|
1 |
Rated Voltage |
kV |
12 |
24 |
|
2 |
Rated current |
A |
630 |
|
3 |
Rated frequency |
Hz |
50/60 |
|
4 |
1 min Power frequency withstand voltage |
Common value |
KV |
42 |
50 |
|
Across insulate distance |
kV |
48 |
60 |
|
5 |
Lightning impulse withstand voltage |
Common value |
kV |
75 |
125 |
|
Across insulate distance |
kV |
85 |
145 |
|
6 |
Rated short time withstand current 2s |
kA |
25 |
20 |
|
7 |
Rated peak value withstand current |
kA |
63 |
50 |
|
8 |
Second loop power frequency withstand voltage 1min |
kV |
2 |
|
9 |
Partial discharge (1.1 times rated voltage) |
PC |
<=10 |
|
10 |
Rated current breaking times |
Times |
100 |
|
11 |
DC withstand voltage |
kV/15min |
<=52 |
|
12 |
Rated cable charging breaking current |
A |
10 |
10 |
|
13 |
Rated close loop breaking current |
A |
630 |
|
14 |
Rated short circuit breaking current |
kA |
20* |
|
15 |
SF6 gas pressure ( relative pressure) |
Bars |
0.45 |
|
16 |
SF6 gas annual leakage |
|
<0.05%/year |
|
17 |
Mechanism lifetime |
Times |
5000 |
|
18 |
Case protective degree |
|
IP2x |
|
Remark: * adopts gas insulated (SF6) vacuum circuit breaker
 |
| ADF-630 type series cable branch cabinet, an outdoor high-voltage electrical equipment with the rated voltage of 12kV and the rated current of 630A, can be used for the cable connection and branching connection the method of which is simple?flexible?safe and reliable. The cabinet crust is made of 2 millimeters of stainless steel plate which is strong and durable. Charged parts are structured with complete insulation and seal. By the adoption of touchable flood-proof cable head, flood-resistance can be realized to greatly advance the power supply reliability. This product is widely used in city industrial districts, residential districts, business centers, mining areas, airports, railroads, wind power station, switching substations and large-scale enterprises like iron, petrol, chemistry, cement industries etc. as well as other distribution net especially for the reform project of electric network of city road.
The product is in conformity with the standards of GB3804-90, GB311.1-97, GB11033.2-89, GB4028-93, GB11032-2000. | |
|
|
|